PHSC-190-XCR-M PROTECTOWIRE Protectowire Type XCR on Msg Wire(BOX OF 500FT)
Contact us for price breaks on large quantities!
The PHSC-190-XCR-M Protectowire is designed with Type XCR on Msg Wire, providing superior protection and communication capabilities. With a box of 500 feet, this product offers reliable and efficient coverage for all your safety needs. Trust in Protectowire, the leader in fire detection and prevention.
The detector is made in multiple temperature ratings to allow for differences in normal ambient temperature. Guidelines for selecting the proper detector temperature rating are the same as for automatic sprinklers and other heat actuated devices. Refer to the Temperature Rating Chart for proper model selection based upon installation temperature limits. Type EPC consists of a durable flame retardant vinyl outer jacket and is designed for interior commercial and industrial applications. Features of this jacket include low moisture absorption, resistance to many common chemicals, and excellent flexibility at low temperatures. Ideal for demanding environments, the Type EPC detector provides reliable performance and protection, ensuring peace of mind for facility managers and occupants alike.
Protectowire Linear Heat Detector is a proprietary cable that detects heat anywhere along its length. The sensor cable is comprised of two steel conductors individually insulated with a heat sensitive polymer. The insulated conductors are twisted together to impose a spring pressure between them, then wrapped with a protective tape and finished with an outer jacket suitable for the environment in which the detector will be installed. This innovative design enables reliable and accurate heat detection in a wide range of applications, from industrial processes to fire protection systems.
Specifications:
Brand | PROTECTOWIRE |
Manufacture | Protectowire Company, Inc. |
Unit of Measurement | FT (Feet) |
TYPE | Cable |
Condition | New |
Weight | 8.0 lbs. |
Model | PHSC |
Length | 500 feet |
Features:
- Line coverage. continuous sensitivity.
- Seven alarm temperature ratings.
- The ability to withstand severe environmental conditions.
- Approval for use hazardous locations.
- Ease of installation, testing, and splicing.
- Compatibility with other initiation devices on same circuit.
- Listed for spacing up to 50 ft. (15.2m).