Macurco Gd-6 White Combustible Fixed Gas Detector
Contact us for price breaks on large quantities!
Macurco GD-6 WHITE Combustible Gas Detector, Controller and Transducer, 12-24VAC or 12-48VDC, White Housing
The GD-6 is a versatile, easy-to-use device that allows you to select between methane, propane or hydrogen gas detection. Combustible gas detectors will respond to a wide range of hydrocarbons, including aerosol sprays, cleaning solvents, paint thinner and other common volatile organic compounds. This low voltage detector provides automatic feedback and fan or valve control that can help reduce combustible gas concentrations in parking garages, battery rooms, maintenance facilities, and other locations that require combustible gas detection.
Features
- White housing
- 12-24VAC or 12-48VDC input
- Alarm relay is activated if gas reaches or exceeds the alarm settings
- Low level meter capable of displaying from 0-50% LEL EX Display, Control & Calibration
- Selectable (on/off) digital display, buzzer, fan delay minutes), fan minimum run time
- Selectable fan and alarm relay activation
- Factory calibrated. Can also be field calibrated using 10% LEL Methane, 10% LEL Propane, or 10% LEL Hydrogen gas, regulator and calibration hood
- One screw allows access for calibration
- Supervised system design: internal detector malfunction will cause the fan & alarm relay to activate
- ETL Listed to UL 61010-1
Specifications
- Power: 3 W (max) from 12 to 24 VAC (Volts Alternating Current) or 12 to 48 VDC (Volts Direct Current)
- Current @ 24VDC: 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
- Shipping Weight: 1 pound (0.45 kg)
- Size: 4 1/2 x 4 x 2 1/8 in. (11.4 X 11.4 X 5.3 cm)
- Color: White
- Connections: plugs/terminals
- Mounting box: (not included) 4x4 electric
- Fan relay: 5 A, 240 VAC, pilot duty, SPDT
- Fan relay actuation: selectable at 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 (default), 11, 12, 13, 14, 15, 16, 17, 18, 19, 20% LEL
- Fan Delay Settings of 0, 1, 3 (default), 5 and 10 minutes
- Fan Minimum Run Time settings are OFF (default), 3, 5, 10 or 15 minutes
- Alarm relay: 0.5A 200 V, 10 VA
- Alarm relay actuation: selectable N.O. default or N.C.
- Alarm relay settings: OFF, 5, 10, 15, 20 (default), 25% LEL
- Current loop, 4-20 mA for 0-50% LEL
- Operating environ: 0F to 125F (-18C to 52C).10 to 90% RH