Upgrade your fire safety system with the FA-301-12DDR Mircom Fire Panel, featuring a microprocessor-based design and 12 initiating devices for efficient and reliable detection. With 4 indicating circuits and a 2 line UDACT digital communicator, this panel supports multiplexed annunciators and smart relays for advanced functionality. Stay informed with alarm and event logs, all powered by a 5 amp power supply.
Specifications:
Brand | MIRCOM |
Manufacture | Mircom Group of Companies |
Unit of Measurement | EA (Each) |
TYPE | Control Panel |
Condition | New |
Weight | 16.0 lbs. |
Features:
- Listed to UL 864, 9th edition
- Available in 6 and 12 zone models
- Integrated UDACT/Digital Communicator on select models
- Equipped with 2 line by 20 character back-lit LCD display and numerical keypad
- Front panel and PC programmable
- Remote upload/download capabilities
- Base panel is equipped with Class “B” (Style “B”) initiating circuits which may be configured as Class “A” (Style “D”) using a Class “A” converter module
- Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only
- Base panel is equipped with Class “B” (Style “B”) indicating circuits which may be configured as Class “A” (Style “Z”) using a Class “A” signal converter module
- Audible signals may be configured for Steady, Temporal Code, California Code and March Time
- Indicating Circuits may be configured as Silenceable or Non-Silenceable for both signals and strobes
- Built-in sync protocols for the following strobe manufacturers: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock
- Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble
- Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
- Subsequent Alarm, Supervisory, and Trouble operation