HONEYWELL V5055A1228 4 FLG GAS VALVE BODY W/V4055
Contact us for price breaks on large quantities!
This Honeywell gas valve body features a 4 FLG design and is compatible with the V4055 model. Made with high-quality materials, it ensures efficient and safe gas flow for your heating needs. Trust in Honeywell's expertise for reliable and durable gas valves. Safety shutoff valves used with V4055, V4062 and V9055 fluid power actuators to control gas flow to commercial and industrial burners. Optimized for precision control and maximum reliability, this valve body is the ideal solution for demanding applications.
Specifications:
Brand | HONEYWELL |
Manufacture | Honeywell International Inc. |
Unit of Measurement | EA (Each) |
TYPE | Millivolt Gas Valve |
Condition | New |
Weight | 33.5 lbs. |
Capacity (CFH) | 10200 |
Max Temp (F) | 150°F |
Temperature Range (F) | -40°F to 150°F |
Min Temp (F) | -40°F |
Used With | V9055 Series, V4055 Series, V4062 Series |
Size | 4" |
Fuel Type | Natural Gas, Propane |
Features:
- Use with natural or LP gases.
- Mount directly in gas supply line.
- Include 1/4 in. NPT upstream and downstream taps and plug.
- 4 in. models have only flanged connections.
- V5055 normally closed valves are rated for final shutoff service safety shutoff.
- V5055A,C,D,E Valves are for On-Off service.
- V5055B Valve has a characterized guide and in combination with the V4055, V4062, and V9055 Fluid Power Actuators, provides slow-opening, hi-lo-off, and modulating functions respectively.
- V5055C,E,F Valves have a double seal and are used with V4055D,E Actuators to provide proof-of-closure switch and valve seal over-travel interlock.
- V5055D,E,F Valves are for high pressure applications.