Kidde Commercial VM-1R FACP, complete system with User Interface, cpu, 1 Loop w/ 2nd loop expansion, 4 class b NAC's, Universal 110/220v 10 amp power supply, Red door, English, order VM-SLC for second loop
Contact us for price breaks on large quantities!
Enhance your commercial fire safety system with the Kidde Commercial VM-1R FACP. This complete system comes with a User Interface, cpu, 1 Loop w/ 2nd loop expansion, 4 class b NAC's, and a Universal 110/220v 10 amp power supply. Its red door adds a professional touch and it can be ordered with VM-SLC for a second loop.
Specifications:
Brand | Kidde Commercial |
Manufacture | Kidde Global Solutions |
Unit of Measurement | EA (Each) |
TYPE | Control Panel |
Condition | New |
Weight | 28.0 lbs. |
Dimensions | 21.7 × 3.5 × 35.5 in |
Color | Red |
Features:
- One Class A or Class B intelligent device loop standard, optional loops brings control panel capacity to 1000 devices
- 24-line by 40-character backlit LCD capable of displaying eight simultaneous events
- Optional voice evacuation and firefighter’s telephone
- Part of an end-to-end audio solution suitable for low frequency signaling in sleeping areas
- Optional network interface slots are located on the back of a swingable mounting chassis
- Electronic addressing with automatic device mapping
- Optional Ethernet port for diagnostics, programming
- Supports strobe synchronization
- Supports up to 30 R-Series remote annunciators with either Class A or Class B wiring
- Networkable up to twenty four VM control panels monitoring 24,000 intelligent points
- Patented Voltage BoostTM technology delivers constant voltage on NAC and AUX circuits — even at low battery power.
- 10 Amp UL listed power supply with universal 94 to 264 Vac input voltage
- Integrated Carbon Monoxide gas sensing with V-PCOS detectors including distinct audible signaling
- Four on-board Notification Appliance Circuits
- Room for three optional front panel LED/Switch modules
- Optional Ethernet interface
- UL2572; UL864 UUKL; UL 864 Listed for releasing applications using GSA-REL
- Optional earthquake hardening: seismic Importance Factor 1.5