This Honeywell V110E1004 1/2 Nonelec Vlv/Npt/Vert is a versatile and reliable valve that can be used in various applications. With its 1/2 inch size and non-electric design, it provides precise control and easy installation. Its vertical orientation also allows for efficient use of space. Trust in Honeywell for top quality valves.

High-Capacity Thermostatic Radiator Valves ensure automatic room temperature control in two-pipe systems by modulating hot water or steam flow through radiators, convectors, and high-capacity heating units.

Specifications:

Brand HONEYWELL
Manufacture Honeywell International Inc.
Unit of Measurement EA (Each)
TYPE Valves
Condition New
Weight 1.55 lbs.
Application Hot Water, 2 Pipe Steam
Application Hot Water, 2 Pipe Steam
Size 1/2"
Max Pressure (PSI) 15 (Steam), 150 (Hot Water)
Body Pattern Angle
Connection Type FNPT x MNPT Union
Capacity High
Flow Capacity (Cv) 4.6
Flow Capacity (Cv) 4.6
BTU 127000 BTU/hr (Steam)
Position Normally Open
Temperature Range (F) 248°F Max
Differential 17 psi
Material Nickel Plated Bronze


Features:

  • Continually monitors and adjusts room temperature for consistent comfort and relief from under-heating and overheating.
  • Designed with the higher capacity normally required by U.S.A. heating systems.
  • Valve seat disc, which is made of resilient material (EPDM), ensures tight shutoff on steam or hot water systems.
  • Nickel-plated bronze casted body with working parts in cartridge insert for ease of service.
  • Controls include sensor, setpoint dial and valve actuator; components may be integral or connected by capillary tubes.
  • Require no electrical connections.
  • All working parts are replaceable using service tool (MT100C1011) while valve remains in service, in-line, under pressure.
  • Valves normally open without control mounted.
  • Valves may also be used with MV110 Electric Zone Valve Actuator.
  • Meet ASHRAE Standard 102-1989.