NCA-2 NOTIFIER Network Control Annunciator
Contact us for price breaks on large quantities!
NCA-2 NOTIFIER Network Control Annunciator
Network Control Annunciator – Second Generation – 640 Characters.
The NOTIFIER NCA-2 is a second-generation Network Control Annunciator for the NOTI•FIRE•NET network, compatible for use with ONYX® Series nodes such as the NFS2- 3030, NFS-3030, NFS-320, NFS-640 and NFS2-640 fire alarm control panels, as well as first-generation NCA Network Control Annunciators. Additionally, the NCA-2 may be configured with DVC Series products to create one or more Digital Audio Command Centers on NOTI•FIRE•NET. The NCA-2 provides system control and display capabilities for all, or for selected network nodes.
The NCA-2 display consists of a 640-character backlit LCD display, and a control interface consisting of “soft” keys used to navigate screen menus, “hard” keys with fixed control functions, and a QWERTY keypad.
When connected to one or more networked panels the NCA-2 provides network control and status/history display capabilities. It may also be configured as the Primary Display for displayless nodes on the network.
Specifications
Weight | 2.00 lbs |
---|---|
Series | |
Manufacturer |
Honeywell International |
Unit of Measurement |
EA (Each) |
Condition |
New |
Compatibility | |
Brand | |
Production Status |
Active |
Listings & Approvals |
CSFM, FM, MEA, UL, ULC |
Features
- Individual Enable/Disable or Group Enable/Disable local for networked ONYX series panels.
- Control ON/OFF networked ONYX series panel control points.
- Read Status networked ONYX series panel points and zones.
- Network paging control/HVAC control .
- Network-wide: Acknowledge, Silence, Reset.
- Lamp Test (local to NCA-2).
- History Buffer (1000 Alarm events; 4000 System events).
- Print NCA-2 programming and history reports.
- Report status of networked panels and their respective field devices to a central station via a single UDACT-2 (see data sheet DN-60686).
- One Master level, nine User level passwords. The Master can assign each User access levels (programming, alter status).
- Interactive Summary Event Count display, event handling package.
- Online programming and alter-status programs.
- Intuitive user guidance program including interactive soft keys.
- Enhanced Read Status/Alter Status displays.
- New history filters for report displaying and printing: All Events, Only Alarms, Only Troubles, Only Supervisory, Only, Security, Time Interval, Point Range.
- Fully programmable node-mapping subsystem.
- Advanced/Basic Walk-Test program.
- Timer control for Auto Silence, AC Fail Delay.
- NCA-2 Meets Canadian ULC display requirements.
- Environmental adjustment controls to maximize LCD legibility.