HYDROLEVEL CG450-1560 CUT-OFF
Contact us for price breaks on large quantities!
HYDROLEVEL CG450-1560 CUT-OFF Intermittent Level Test Maximum Protection for Foaming Boilers. The HYDROLEVEL CG450-1560 CUT-OFF is designed to provide reliable and accurate level measurement in high-foaming boiler applications. This intermittent level test ensures maximum protection against false trips and unnecessary downtime, while its advanced sensors and algorithms guarantee precise monitoring and control.
Specifications:
Brand | HYDROLEVEL |
Manufacture | Hydrolevel Company |
Unit of Measurement | EA (Each) |
TYPE | Water Boilers |
Condition | New |
Weight | 7.0 lbs. |
Application | Steam Boilers |
Switch | SPDT |
Max Pressure (PSI) | 15 (Steam) |
Type | Electronic |
Voltage | 120v |
Power Consumption | 4.2 VA |
Reset Type | Automatic |
Electrical Ratings (AFL) | 5.8 A @ 120 VAC (N.C) |
Electrical Ratings (ALR) | 34.8 A @ 120 VAC (N.C) |
Features:
- 15 Second Burner Off Delay
- 30 Second Burner On Delay
- Automatic Reset
- Low Water Indicating Light
- Direct Boiler Mounting – Eliminates Blowdowns Burner circuit contacts open after 15 second delay in a low water condition. Delay prevents short cycling caused by momentary fluctuations in the boiler water level. Automatically reactivates burner circuit 30 seconds after water reaches the probe, allowing optional water feeder to raise water level above the probe. Intermittent Level Test (ILT) feature provides maximum boiler protection by removing power from the burner circuit at set intervals.