Notifier NFW-50X Intelligent Addressable Fire Alarm Control Panel with Communicator
Contact us for price breaks on large quantities!
Notifier NFW-50X Intelligent Addressable Fire Alarm Control Panel with Communicator.
The NFW-50X Notifier is the latest intelligent addressable fire alarm control panel (FACP) within the FireWarden Series and is a direct replacement for the FireWarden-50 (NFW-50). The NFW-50X comes with a pre-installed communicator and supports up to 50 addressable devices in any combination of detectors or modules. With an extensive list of powerful features, the NFW-50X programs just like FireWarden-100 products, yet fits into applications previously served only by conventional panels. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel’s USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system voltages by means of a USB flash drive.
Additional information
Weight | 16 lbs |
---|---|
Manufacturer |
Honeywell |
Brand |
Notifier |
Condition |
New |
Type |
Control Panel |
Style |
Addressable |
Color |
N/A |
Series |
N/A |
Production Status |
Active |
Compatibility |
N/A |
Features
- Listed to UL Standard 864, 10th edition.
- Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Telephone Service) Central Station Communicator.
- Optional CELL-MOD or CELL-CAB-N GSM Central Station Communicator over AlarmNet®.
- Compatible with SWIFT® wireless devices.
- Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address.
- Two independently programmable, built-in Style Z (Class A) or Style Y (Class B) NAC circuits.
- Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices.
- Notification Appliance Circuit End of Line resistor matching.
- Four programmable function keys for ease of maintenance.
- Two programmable relays and one fixed trouble relay.
- Built-in Programmer.
- Integral 80-character LCD display with backlighting.
- Real-time clock/calendar with automatic daylight savings control.
- History file with 1,000 event capacity.
- Addressable sounder base.
- Control module delay timer.
- Automatic detector sensitivity testing (NFPA 72 compliant).
- Automatic device type-code verification.
- Point trouble identification.
- Waterflow selection per module point.
- Alarm verification selection per detector point.
- Maintenance alert warns when smoke detector dust accumulation is excessive.
- One-person audible or silent walktest with walktest log & printout.
- System alarm verification selection per detector point.
- PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant).
- Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus.
- Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator.
- Upload/Download of program and data via USB with optional FSTools Programming Utility.